0026120 is listed in CLASSIC FD 810 as 3G0.75 mm² with a 6.2 mm diameter. Class 6 conductors provide the construction basis for control connections bending in a cable chain. For this PVC-sheathed article, moving-use temperature limits differ from fixed-installation limits.
Application selection
Compare the moving environment with the catalogue range of 0 to +70 °C.
Technical specifications
| Model | 0026120 |
|---|---|
| Cores x cross-section (mm²) | 3 G 0.75 |
| Outer diameter (mm) | 6.2 |
| Copper index (kg/km) | 22 |
| Weight (kg/km) | 60 |
| Rated voltage | 300/500 V |
| Conductor class | 6 |
| Sheath | PVC, grey |
| Moving / fixed bend radius | 7.5D / 4D |
| Protective conductor | Included (G) |
D is cable outer diameter. Published dimensions do not replace checks of current, motion and termination for the application.
Does the fixed-installation low-temperature limit apply while moving?
No. The FD 810 record specifies different temperature ranges for fixed and moving use.
Request a quotation
Send temperature, stroke and metre requirements for 0026120.
Price, stock, cut lengths or quantities and delivery require confirmation.
Compare related articles