Phoenix Contact MINI MCR-2-UI-UI-PT 2902040 Signal Conditioner
A 6.2 mm, 3-way isolated analog signal conditioner for configurable current/voltage conversion, amplification and filtering via DIP switches.
Verified technical specifications, selection, installation and commissioning notes for Phoenix Contact MINI MCR-2-UI-UI-PT, with Automation engineering and technical-service support.
Verified technical data
- Channels: 1
- Isolation: 3-way
- Supply: 24 VDC nominal; 9.6…30 VDC
- Inputs: 0/4–20 mA, -20…20 mA and multiple ±30 V ranges via DIP switch
- Outputs: 0/4–20 mA and multiple ±10 V ranges
- Transmission error: ≤0.1% of configured output-range maximum (general condition)
- Filter: 30 Hz or 5 kHz via DIP switch
- Configuration: DIP switches; NFC supported
- Connection: Push-in
- Protection: IP20
Selection criteria
Choose exact input and output ranges from the supported DIP-switch table. Check 9.6…30 VDC supply and load requirements. Select 30 Hz or 5 kHz filter behavior to suit signal dynamics. Confirm 3-way isolation and Ex approvals meet project requirements.
Installation, commissioning and maintenance
Mount on DIN rail and use Push-in wiring within documented conductor sizes. Maintain proper isolation/segregation for the application. Set DIP switches before energization and verify configured range end points. Test zero/span and response with a calibrated source where accuracy is critical. Document DIP configuration and inspect wiring/power status during service.
Source policy: Numeric technical claims are taken only from current official manufacturer sources. No price, stock, lead-time, warranty, distributor or partnership claim is included.