Technical description and application scope
Beckhoff EK1100 EtherCAT Coupler
The EK1100 couples 100BASE-TX EtherCAT networks to Beckhoff ELxxxx EtherCAT terminals through two RJ45 interfaces.
Verified technical specifications, selection, installation and commissioning notes for Beckhoff EK1100, with Automation engineering and technical-service support.
Verified technical data
- Function: Coupling EtherCAT terminals (ELxxxx) to 100BASE-TX EtherCAT
- Protocol: EtherCAT
- Data rate: 100 Mbit/s
- Bus interface: 2 x RJ45
- Cable length between stations: max. 100 m
- EtherCAT terminals: up to 65,534 in technical data
- Propagation delay: approx. 1 µs
- Supply: 24 V DC (-15%/+20%)
- E-bus supply: 2000 mA
- Power contacts: max. 24 V DC / 10 A
- Electrical isolation: 500 V
Selection criteria
Calculate total E-bus current and add power-feed terminals when required. Respect the 100 m maximum 100BASE-TX segment length. Check field power-contact voltage/current and isolation needs. Verify IP20 cabinet environment and temperature limits.
Installation, commissioning and maintenance
Mount on a 35 mm DIN rail and maintain suitable cabinet environmental protection. Connect system/field 24 VDC and EtherCAT in/out ports according to the official topology. Scan the EtherCAT station in TwinCAT, verify terminal order and process image. Check link/run/error diagnostics and distributed I/O operation under machine load. Inspect RJ45 latching, power contacts and terminal seating; retain TwinCAT configuration and ESI/version documentation.
Source policy: Numeric technical claims are taken only from current official manufacturer sources. No price, stock, lead-time, warranty, distributor or partnership claim is included.