Technical description and application scope
Pepperl+Fuchs KFD2-SR3-Ex2.2S 69738 Isolated Barrier
A two-channel K-System isolated barrier/switch amplifier for NAMUR or dry-contact inputs with relay outputs and SIL 2 capability.
Verified technical specifications, selection, installation and commissioning notes for Pepperl+Fuchs KFD2-SR3-Ex2.2S, with Automation engineering and technical-service support.
Verified technical data
- Channels: 2
- Supply: 19…30 VDC via Power Rail or terminals
- Rated current: 30…20 mA
- Power consumption: <600 mW
- Inputs: Dry contact or NAMUR
- Open-circuit / short-circuit input: approx. 10 VDC / approx. 8 mA
- Switch point / hysteresis: 1.2…2.1 mA / approx. 0.2 mA
- Outputs: 2 × 2 relay contacts with AND logic
- Contact loading: 48 VAC/1 A or 40 VDC/1 A resistive
- Safety: SIL 2, SC3
- Protection: IP20
Selection criteria
Verify NAMUR/dry-contact input type and required relay logic. Check Ex entity parameters and hazardous-area certificate compatibility. Confirm SIL target and proof-test/application requirements. Check relay load against the verified contact rating.
Installation, commissioning and maintenance
Install on 35 mm DIN rail and Power Rail only per Pepperl+Fuchs instructions. Maintain hazardous/non-hazardous wiring segregation and certification requirements. Verify 19…30 VDC supply and channel mode/DIP settings. Test line-fault detection and relay outputs with representative field devices. Include functional proof testing where required by the safety lifecycle. Inspect field wiring and monitor LFD indications during service.
Source policy: Numeric technical claims are taken only from current official manufacturer sources. No price, stock, lead-time, warranty, distributor or partnership claim is included.