Technical description and application scope
Pepperl+Fuchs NBB5-18GM50-E2-10M technical overview
Verified technical specifications, selection, installation and commissioning notes for Pepperl+Fuchs NBB5-18GM50-E2-10M, with Automation engineering and technical-service support.
Verified technical data
- Anahtarlama: Normalde açık (NO), PNP, 3 telli
- Anma algılama mesafesi: 5 mm, flush
- Besleme: 5…36 VDC
- Anahtarlama frekansı: 0…1950 Hz
- Çıkış akımı: 0…200 mA
- Gerilim düşümü: ≤1 V
- Bağlantı: 10 m PVC kablo, 3 damarlı
- Gövde: Pirinç, beyaz bronz kaplama; M18
- Koruma: IP65 / IP66 / IP67 / IP68
Selection and application
Match PNP/NO output to the PLC input circuit. Keep the 5 mm rated flush sensing distance and target-material reduction factors in mind. Confirm 10 m fixed PVC cable suits routing and flex conditions. Validate temperature and ingress-protection requirements.
Installation, commissioning and maintenance
Install flush in metal in accordance with the official sensor geometry. Do not exceed the documented M18 tightening torque of 30 Nm. Route the 10 m cable to protect it from repeated bending below the documented bend radius. Verify 5…36 VDC supply and PNP input wiring. Test switching with the actual target material and required safety margin. Confirm yellow switching LED and PLC status agree. Keep sensing face free of metal buildup that changes the application gap. Inspect cable sheath and mounting torque during planned stops.
Source policy: Numeric technical values are taken only from the current official manufacturer product page or official technical documentation. No price, stock, lead-time, warranty or distributor claim is included.